Methods of Solving A.C. Distribution Problems

       As discussed in earlier section of a.c. distribution system we have take into account the power factor. This power factor can be either considered with respect to receiving end voltage or with respect to load voltage itself. Let us consider each case separately.
1.1 Power Factors Referred to Receiving End Voltage 
       Consider an A.C. distribution PQ having concentrated loads of I1 and I2 tapped off at point Q and R respectively. This is shown in the Fig. 1.
Fig. 1

        Let voltage VQ which is the voltage at the receiving end be taken as reference vector. The power factors at R and Q are cosΦ1 and cosΦ2 with respect to VQ and they are lagging.
Let,             R1  = Resistance of section PR
                  X1 = Reactance of section PR
                  R2 = Resistance of section RQ
                  X2 = Reactance of section RQ
       Impedance of section PR is given by,

       Impedance of section RQ is given by,

       The load current at point R is  Ī1,

       Similarly the load current at point Q is Ī2,

       The current in section RQ is nothing but Ī2,

       The current in section PR is given by,

       The voltage drop in section RQ is given by,

       The voltage drop in section PR is given by,

       Thus the sending end voltage VA is given as,

       The sending end current is given as,

       The corresponding phasor diagram is shown in the Fig. 2.
Fig. 2

       As shown in the Fig. 2. the receiving end voltage VQ is taken as reference vector. The currents  I1 and I2 are lagging from VQ by angles of Φ1 and Φ2 respectively. The vector sum of I1 and I2 gives current IPR. The drop is I2R2 in phase with I2  while I2X2 is leading by 90o. The vector sum of VQ, I2R2 and I2X2 gives VR. The drop  IPRR1 is in phase with current IPR while IPRX1  is leading by 90. The vector sum of VR, IPRR1 and IPRX1 gives the sending end voltage.
1.2 Power Factors Referred to Respective Load Voltages
      In previous section we have considered the load power factors with respect to receiving end voltage. Here we will consider these power factors with respect to their respective load voltages. Now Φ1 is the phase angle between VR and I1 while the angle Φ2 is the phase angle between VQ  and I2.
       The phasor diagram under this condition will be as shown in the Fig. 3.
Fig. 3

       Here again the receiving end voltage VQ is the reference phasor. The vector sum of I1 and I2 gives the current IPR. The drop I2R2 is in phase with I2 while I2X2 is leading by 90. The vector sum of VQ, I2R2 and I2X2 gives voltage VR. The drop IPRR1  is in phase with current IPR while the drop IPRX1 is leading by 90o. The vector sum of VR, IPRR1 and IPRX1 gives the sending end voltage Vp.
       Now voltage drop in section RQ is given by,

...   The sending end voltage Vp is given by,

Read Solved Examples
Methods of Solving A.C. Distribution Problems Methods of Solving A.C. Distribution Problems Reviewed by haru on February 08, 2013 Rating: 5

No comments

Ads Inter Below The Post
Image Link [https://lh3.googleusercontent.com/-wlvSkBWGUW0/AAAAAAAAAAI/AAAAAAAAAxU/6FpWSjn-h2o/s120-c/photo.jpg] Author Name [Sora Templates] Author Description [Lorem Ipsum is simply dummy text of the printing and typesetting industry. Lorem Ipsum has been the industry's standard] Facebook Username [#] Twitter Username [#] GPlus Username [#] Pinterest Username [#] Instagram Username [#]