Impulse Voltage Tests of Circuit Breaker and Standard Impulse Waves


This test is necessary for all indoor and outdoor breakers. The test is carried out as follows: Standard impulse wave of specified amplitude is applied five times in succession.

If flash-over or puncture of insulators does not occur, the circuit-breaker is considered to have passed the test. If puncture occurs or if on two or more applied test wave flash-over occurs, the circuit breaker is considered to have failed the test. During the test some waves should be applied with reversal of polarity.

The impulse voltage wave is generated in an Impulse Voltage Generator. During the test one terminal of the impulse generator is connected to the terminal of the circuit breaker pole. The other terminal is connected to the earth and the frame of the circuit breaker.

Standard lightning Impulse is a full impulse having a front time 1.2 �sec and time to half value of 50 �sec. It is described as 1.2/50 impulse as shown in figure below.



Standard switching impulse wave is characterized by prolonged wave-front and wave tail. The typical switching impulse wave has front fen of the order of 250 �s and half time of 2500 �s. The permissible deviation in the crest vale is of the order of 4 to 12%.


The switching impulse wave has been specified for high voltage circuit-breaker rated 420 kV and above.
Impulse Voltage Tests of Circuit Breaker and Standard Impulse Waves Impulse Voltage Tests of Circuit Breaker and Standard Impulse Waves Reviewed by haru on October 15, 2016 Rating: 5

No comments

Ads Inter Below The Post
Image Link [https://lh3.googleusercontent.com/-wlvSkBWGUW0/AAAAAAAAAAI/AAAAAAAAAxU/6FpWSjn-h2o/s120-c/photo.jpg] Author Name [Sora Templates] Author Description [Lorem Ipsum is simply dummy text of the printing and typesetting industry. Lorem Ipsum has been the industry's standard] Facebook Username [#] Twitter Username [#] GPlus Username [#] Pinterest Username [#] Instagram Username [#]